Windows Update後所有風扇都顯示錯誤
After a Windows update and one restart the server reported that all the FANs are faulty even if the fans are working fine in the chassis – at full speed.
The alers were generated into iMana also the front LCD gave the error from F01 to F05. The customer just only made a windows update without any other physicaly intervention on the server, after the windows update a restart was required.
These alers were generated after the first restart after the windows update.
Solution
These alarms will not affect the good working of the server or the application from that server.
These are occasionally caused by server power-on and power-off. Like a solution we have to upgrade the version of iBMC to V202, which resolve this issue.
RH1288 V3-iBMC-V202.zip
In below we have a guide for how to do the upgrade:
HUAWEI Rack Server Upgrade Guide (iBMC)